OleumTech WT-AD1
OleumTech WT-AD1 is a wireless i/o module running Proprietary 900 MHz / Proprietary 2.4 GHz on 900 MHz / 915 MHz ISM (FHSS), 2.4 GHz (DSSS), 868 MHz (LBT-AFA) with 1 DI · 3 AI in a IP66 enclosure.
OleumTech OTC wireless network (to an OTC gateway) Proprietary 900 MHz / Proprietary 2.4 GHz · 900 MHz / 915 MHz ISM (FHSS) · 2.4 GHz (DSSS) · 868 MHz (LBT-AFA) Field I/O — 1 DI · 3 AI
- Tx power
- 18 dBm
- Sensitivity
- -110 dBm
- Range class
- 2.3 km — Up to 7500 ft / 1.4 miles (2.3 km) with clear line of sight at 900/915 MHz, transmitter to gateway; 2.4 GHz up to 3.1 km, 868 MHz up to 2.4 km (datasheet; maximum-range figures collected under optimal test conditions)
Wireless identity
| Parameter | Value | Source |
| Protocol | Proprietary 900 MHz · Proprietary 2.4 GHz | 67-4040-001_S (manufacturer datasheet) |
| Frequency band | 900 MHz / 915 MHz ISM (FHSS) · 2.4 GHz (DSSS) · 868 MHz (LBT-AFA) | 67-4040-001_S (manufacturer datasheet) |
| Transmit power | 18 dBm (Maximum, 2.4 GHz model (63 mW); 900/915 MHz models 10 mW, 868 MHz model 25 mW (datasheet 67-4040-001_S)) | 67-4040-001_S (manufacturer datasheet) |
| Receiver sensitivity | -110 dBm (900/915 MHz at 9600 bps; -100 dBm at 115.2 kbps, 2.4 GHz -101 dBm at 250 kbps, 868 MHz -106 dBm at 80 kbps (datasheet)) | 67-4040-001_S (manufacturer datasheet) |
| Range class | 2.3 km — Up to 7500 ft / 1.4 miles (2.3 km) with clear line of sight at 900/915 MHz, transmitter to gateway; 2.4 GHz up to 3.1 km, 868 MHz up to 2.4 km (datasheet; maximum-range figures collected under optimal test conditions) | 67-4040-001_S (manufacturer datasheet) |
I/O and electrical
| Parameter | Value | Source |
| I/O counts | 1 DI · 3 AI | 67-4040-001_S (manufacturer datasheet) |
| I/O notes | 3 analog inputs (0-5 Vdc, 24-bit ADC) and 1 discrete input (dry contact or open-drain/NPN). The transmitter supplies up to 9.5 Vdc of power to connected analog sensors (datasheet). | 67-4040-001_S (manufacturer datasheet) |
| Upstream interfaces | OleumTech OTC wireless network (to an OTC gateway) | 67-4040-001_S (manufacturer datasheet) |
| Power supply | Self-contained internal 3.6 Vdc lithium battery pack (replaceable; OleumTech SX1000-BP3 only) | 67-4040-001_S (manufacturer datasheet) |
| Battery life | Up to 10 years — Ambient temperature and one transmission per 1-minute interval without any retries (datasheet footnote 1; see the OleumTech Battery Life Expectancy Chart for other intervals) | 67-4040-001_S (manufacturer datasheet) |
Environment and certifications
| Parameter | Value | Source |
| Ingress rating | IP66 | 67-4040-001_S (manufacturer datasheet) |
| Operating temperature | -40 °C to +70 °C | 67-4040-001_S (manufacturer datasheet) |
| Hazardous area | Class I Division 1, Groups A-D, T3C — intrinsically safe (Ex ia IIC T3); Class I Zone 0, AEx ia IIC T3 | 67-4040-001_S (manufacturer datasheet) |
| Certifications | FCC Part 15 (USA) · IC ICES-003 (Canada) · ACMA (Australia) · ATEX Sira 13ATEX2142X · IECEx SIR 13.0054X | 67-4040-001_S (manufacturer datasheet) |
Other recorded products on the same protocol
Source
Every figure on this page was transcribed from the manufacturer's own
documentation: 67-4040-001_S (manufacturer datasheet),
checked 2026-11-14. Figures the source
does not state are not estimated and do not appear. The full database,
including records still being completed, is on the product database index.